Figure 3. Setting Yokogawa UT150 temperature controller for Heatec fuel preheaters
Prompt Description
(what it does)
Settings (use up/down arrow keys)
(green characters are actual settings)
(what you see) (what it means)
Setup Parameters
IN Input type 35: J -300 to 2100° F
SPH Setpoint range maximum value 190
SPL Setpoint range minimum value 0
UPR Setpoint ramp-up rate OFF
DNR Setpoint ramp-down rate OFF
TMU Sepoint ramp-rate time limit 1: °F/min
RTH Retransmission maximum value 190
RTL Retransmission minimum value 0
AL1 Alarm 1 type 2: Low Limit Alarm
AL2 Alarm 2 type 1: High Limit Alarm
HY1 Alarm 1 hysteresis 0
HY2 Alarm 2 hysteresis 0
SC SUPER function ON
DR Direct / reverse action 0: Reverse action
Operating Parameters
A/M Auto / Manual AUT
A1 A1 Value 155
A2 A2 Value 212
CTL Control Mode PID
AT Auto-tuning OFF
P Proportional Band 24
I Integral time 256
D Derivative time 64
FL PV input filter OFF
BS PV input bias 0
LOC Key lock 0: No key lock