Figure 3. Setting Yokogawa UT150 temperature controller for Heatec fuel preheaters
Prompt
Description
(what it does)
Settings (use up/down arrow keys)
(green characters are actual settings)
(what you see)
(what it means)
Setup Parameters
IN
Input type
35
: J -300 to 2100° F
SPH
Setpoint range maximum value
190
SPL
Setpoint range minimum value
0
UPR
Setpoint ramp-up rate
OFF
DNR
Setpoint ramp-down rate
OFF
TMU
Sepoint ramp-rate time limit
1
: °F/min
RTH
Retransmission maximum value
190
RTL
Retransmission minimum value
0
AL1
Alarm 1 type
2
: Low Limit Alarm
AL2
Alarm 2 type
1
: High Limit Alarm
HY1
Alarm 1 hysteresis
0
HY2
Alarm 2 hysteresis
0
SC
SUPER function
ON
DR
Direct / reverse action
0
: Reverse action
Operating Parameters
A/M
Auto / Manual
AUT
A1
A1 Value
155
A2
A2 Value
212
CTL
Control Mode
PID
AT
Auto-tuning
OFF
P
Proportional Band
24
I
Integral time
256
D
Derivative time
64
FL
PV input filter
OFF
BS
PV input bias
0
LOC
Key lock
0
: No key lock
←
previous
© 2004 Heatec, Inc
Home
|
Profile
|
Products - Asphalt
|
Products - Industrial
|
Products - Concrete
Literature
|
Tec-Notes
|
Parts
|
Service
|
Employment
|
Contacts
Please contact
Heatec, Inc.
at
Phone (423) 821-5200 | Toll-Free (800) 235-5200 | Fax: (423) 821-7673
5200 Wilson Road | P.O. Box 72760 | Chattanooga, Tennessee 37410
©2007 Astec Industries, Inc. All Rights Reserved.
Legal Notice
|
Privacy Policy
|
Webmaster
Back to preheater
Tec-Notes