Figure 2. Insulation thickness vs cost.*


Figure 3. Heatec vertical asphalt storage tanks are insulated on top and bottom as well as sides.


Figure 4. Heatec tanks have 6-inches of Owens-Corning fiberglass insulation (2 layers of 3-inches).

Totaling up heat loss
Conductance is used to determine how much heat a tank loses and is the basis for the information in Figure 5. This figure compares the total amount of heat lost by tanks using insulation of several thicknesses for one year. The figure also shows the amount of fuel it would take to make up for the amount of heat lost. Carefully compare the differences in the amounts of fuel required.

Figure 5. Heat & fuel loss/year

Heat & fuel loss

Tank with 3-inch insulation

Tank with 4-inch insulation

Tank with 5-inch insulation

Tank with 6-inch insulation

Btu

361,971,031

273,598,535

219,998,325

183,869,071

Gallons

No. 2 fuel

2,742

2,073

1,667

1,393

Ccf

Natural gas

4,000

3,023

2,431

2,032

30,000 gallon storage tank. Maintain AC temperature at 300 degrees F. Annual hours of operation is 8760.