PROBLEM
|
PROBABLE CAUSE
|
REMEDY
|
|
High flue gas stack temperature indicator light is off.
|
1. High flue gas stack switch is tripped.
|
1. Remove cover from switch and reset switch.
|
|
2. Strainer is clogged.
|
2. Remove and clean strainer.
|
|
3. Helical coil in heater is coated with soot.
|
3. Remove end cover of heater and clean coil per separate Tec-Note on service.
|
| 4. Inadequate flow of thermal fluid in system piping. |
4. Check for closed or stuck valve in system piping. |
|
Low media level indicator light is off.
|
1. Level of media (thermal fluid) in expansion is too low.
|
1. Add thermal fluid to expansion tank. Also check piping to ensure there are no leaking connections.
|
| 2. Low media level switch in expansion tank is malfunctioning. |
2. Check low media level switch for proper operation per separate Tec-Note on service. |
|
Media level sight gage does not accurately indicate fluid level in expansion tank.
|
1. Two valves on sight gauge not open.
|
1. Open both valves on sight gauge. Use measuring stick through tank filler pipe to confirm accuracy of gauge.
|
| 2. Sludge in expansion tank. |
2. Clean sludge from expansion tank per separate Tec-Note on service. |
|
Burner does not modulate.
|
1. Low fire hold switch in HOLD position.
|
1. Set switch to NORMAL position.
|
|
2. Dip switches of modulating actuator TZ4-1 not set properly.
|
2. Re-set dip switches per settings shown on wiring drawing furnished with heater. Use ball point pen to make sure switches are fully depressed!
|
|
3. Low fire hold temperature of UDC3300 is set too high.
|
3. Reset low fire hold temperature of UDC3300 to a lower temperature.
|
|
4. Defective power transformer in modulating actuator TZ4-1.
|
4. Check the transformer in the actuator and replace it if defective per separate Tec-Note on service.
|
|
5. Defective resistor board in modulating actuator TZ4-1.
|
5. Check the resistor board in the actuator and replace if defective per separate Tec-Note on service.
|
| 6. Defective motor in modulating actuator TZ4-1 |
6. Check the motor in the actuator and replace if defective per separate Tec-Note on service. |
|
Fuel oil pressure low or erratic.
|
Damaged fuel pump drive coupling.
|
Remove blower and coupling, inspect spline for damage and slippage. Replace if damaged.
|