|
|
|
|
 |
|
Cleaning strainer (M, Fig. 9)
- Set the switch marked HEATER CONTROL to OFF (Fig. 5). Allow the circulation pump and the auxiliary pumps (HC heater only) to continue operating for approximately 5 minutes.
- Set the switch labeled CIRC. PUMP to OFF.
- For HC heaters, set all switches labeled AUX. PUMP to OFF.
- Set valves as indicated in Fig. 3 for Clean Strainer. (See also Fig. 4.)
- Place a bucket or other container under the drain valve (Fig. 6). Container should be at least 5-gallon capacity.
NOTE: Wear chemical and heat resistant gloves as shown in Fig. 6.


Figure 6. Drain valve installed in strainer flange.
(Wear chemical and heat resistant gloves as protection from hot oil.)
- Open drain valve to drain thermal fluid from the strainer. Do not re-use this fluid. Dispose of it properly.
- Unbolt the square flange from the bottom of the strainer. Remove the flange, and the strainer basket will slide out.
- Clean the strainer basket with fuel oil, then dry completely with compressed air.
- Re-install the strainer basket and flange.
- Close drain valve.
- Install a cap on the drain valve (Fig. 6) to protect against accidental release of thermal fluid.
Bleeding air from the circulating pump
(P, Fig. 9)
- Make sure that the HEATER CONTROL switch (Fig. 5) is set to OFF.
- Close the valve number 4 (N, Fig.9) in the thermal fluid line at the helical coil inlet.
- Observe coil inlet pressure gauge (Fig. 8). When gauge indicates normal operating pressure, open valve fully at inlet of helical coil. Normal operating pressures are shown in Fig. 7.
- Repeat as necessary until pressure indication is steady at its normal pressure.
|
Figure 7. Gauge Indications For Heater Normal Operation
|
|
Model
|
Fuel Oil Supply Pressure
|
Fuel Oil Return Pressure
|
Coil Inlet
Pressure
|
Coil Outlet
Pressure
|
Coil Outlet Thermometer**
|
Manifold
Thermometer***
|
|
HCS-70
|
275-300 psi
|
70-180 psi
|
50-60 psi*
|
36-46 psi*
|
320°F
|
-
|
|
HCS-100
|
275-300 psi
|
70-180 psi
|
50-60 psi*
|
26-36 psi*
|
320°F
|
-
|
|
HCS-175
|
275-300 psi
|
70-180 psi
|
50-60 psi*
|
29-39 psi*
|
320°F
|
-
|
|
HCS-250
|
275-300 psi
|
70-180 psi
|
50-60 psi*
|
24-34 psi*
|
320°F
|
-
|
|
HC-120
|
275-300 psi
|
70-180 psi
|
50-60 psi
|
0-10 psi
|
320°F
|
< 270°F
|
|
HC-200
|
275-300 psi
|
70-180 psi
|
50-60 psi
|
0-10 psi
|
320°F
|
< 270°F
|
|
HC-300
|
275-300 psi
|
70-180 psi
|
50-60 psi
|
0-10 psi
|
320°F
|
< 270°F
|
|
*These pressures may vary approximately 30 to 40 percent depending upon piping circuits.
**Temperature at coil outlet should be same as set point.
***Temperature at manifold should be approximately 50 or more degrees less than set point. 275-300 psi 70-180 psi 25-30 psi 0-10 psi
|

Figure 8. Left: Outlet pressure gauge. Right: Inlet pressure gauge.
|
|
|
|
|
|
|
|
 |
|
previous page
|
|
next page |
|
|
|
|
|
 |
|
You need Acrobat Reader to view PDFs.
|
|