Figure 3. Honeywell Controller DC2500-EE-1000-200-00000-00-0
used with Siemens Pressure Transmitter on Heatec vertical asphalt tanks
Setup button Function button Make these settings (use up/down buttons)
10,000 gal tank 15,000 gal tank 20,000 gal tank 25,000 gal tank 30,000 gal tank 35,000 gal tank
TUNING CYC T1 1 1 1 1 1 1
  SECUR 0 0 0 0 0 0
  LOCK CAL CAL CAL CAL CAL CAL
               
SPRAMP SPRAMP DIS DIS DIS DIS DIS DIS
               
ALGOR CTRALG ONOF ONOF ONOF ONOF ONOF ONOF
  TIMER DIS DIS DIS DIS DIS DIS
               
OUTALG OUTALG RLY RLY RLY RLY RLY RLY
               
INPUT1 IN1TYP 4-20 4-20 4-20 4-20 4-20 4-20
  XMITR1 LIN LIN LIN LIN LIN LIN
  IN1 HI 600.0 600.0 600.0 600.0 600.0 600.0
  IN1 LO 11.0 11.0 11.0 11.0 11.0 11.0
  RATIO1 1.00 1.00 1.00 1.00 1.00 1.00
  BIAS 1 0.0 0.0 0.0 0.0 0.0 0.0
  FILTR1 1 1 1 1 1 1
  BRNOUT NONE NONE NONE NONE NONE NONE
               
CONTRL LSP'S ONE ONE ONE ONE ONE ONE
  SP TRK NONE NONE NONE NONE NONE NONE
  PWR UP ALSP ALSP ALSP ALSP ALSP ALSP
  SP Hi 0.00 0.00 0.00 0.00 0.00 0.00
  SP Lo 0.00 0.00 0.00 0.00 0.00 0.00
  ACTION REV REV REV REV REV REV
  HYST 100.0 100.0 100.0 100.0 100.0 100.0
  FAILSF 0.0 0.0 0.0 0.0 0.0 0.0
               
OPTION AUXOUT IN 1 IN 1 IN 1 IN 1 IN 1 IN 1
  0 PCT 11.0 11.0 11.0 11.0 11.0 11.0
  100 PCT 600.0 600.0 600.0 600.0 600.0 600.0
  CRANGE 4-20 4-20 4-20 4-20 4-20 4-20
  DIGIN1 NONE NONE NONE NONE NONE NONE
               
COM ComADR 3 3 3 3 3 3
  ComSTA DIS DIS DIS DIS DIS DIS
  IRENAB ENAB ENAB ENAB ENAB ENAB ENAB
  BAUD 19.2k 19.2k 19.2k 19.2k 19.2k 19.2k
  TX DLY 1 1 1 1 1 1
               
ALARMS A1S1TY IN 1 IN 1 IN 1 IN 1 IN 1 IN 1
  A1S1VA 12.00 12.00 18.00 18.00 18.00 18.00
  A1S1HL LOW LOW LOW LOW LOW LOW
  A1S2TY NONE NONE NONE NONE NONE NONE
  A2S1TY IN 1 IN 1 IN 1 IN 1 IN 1 IN 1
  A2S1VA 153.0 249.0 321.0 417.0 489.0 561.0
  A2S1HL HIGH HIGH HIGH HIGH HIGH HIGH
  A2S2TY NONE NONE NONE NONE NONE NONE
  ALHYST 0.1 0.1 0.1 0.1 0.1 0.1
  ALARM1 NO L NO L NO L NO L NO L NO L
  BLOCK DIS DIS DIS DIS DIS DIS
  DIA AL DIS DIS DIS DIS DIS DIS
               
DISPLY DECMAL ONE ONE ONE ONE ONE ONE
  TUNITS NONE NONE NONE NONE NONE NONE
  FREQ 60 60 60 60 60 60
  DISPLY PR N PR N PR N PR N PR N PR N
  LNGUAG ENGL ENGL ENGL ENGL ENGL ENGL
Setting sequence: ALGOR, INPUT1, CONTRL, OPTION, COM, ALARMS, DISPLY, TUNING, SPRAMP, OUTALG.

previous page



Home | Profile | Products - Asphalt | Products - Industrial | Products - Concrete
Literature | Tec-Notes | Parts | Service | Employment | Contacts

Please contact Heatec, Inc. at
Phone (423) 821-5200 | Toll-Free (800) 235-5200 | Fax: (423) 821-7673
5200 Wilson Road | P.O. Box 72760 | Chattanooga, Tennessee 37410

©2007 Astec Industries, Inc. All Rights Reserved.
Legal Notice | Privacy Policy | Webmaster


Asphalt Tank
Tec-Notes