Pages: 1, 2, 3, 4, 5, 6, 7, 8

Figure 3 (Part 1). Programming Honeywell UDC3300
(Modulating Controller) for Heatec HC and HCS heaters

Group
Prompt

(SET UP button)

Function
Prompt

(FUNCTION button)

Value or
Selection

(up / down arrows)

Group Prompt

Function Prompt

Value or
Selection

TUNING

PROP BD

10.0

ALGORTHM

CONT ALG

PID A

  GAIN     TIMER DISABL
  GAINVALn Read Only   PERIOD  
  RATE MIN 1.00   START  
  RSET MIN     LDISP  
  RSET RPM 5.00   INP ALG1  
  MAN RSET     MATH K  
  PROPBD2     CALC HI  
  GAIN 2     CALC LO  
  RATE2MIN     ALG1 INA  
  RSET2MIN     ALG1 INB  
  RSET2RPM     ALG1 INC  
  CYC SEC     PCO SEL  
  CYC SX3     PCT CO  
  SECURITY 0   ATM PRES  
  LOCKOUT CALIB      
  AUTO MAN   OUT ALG OUT ALG CURRNT
  SP SEL     4-20 RNG  
  RUN HOLD     OUT2 ALG  
        RLYSTATE  
SPRAMP SP RAMP DISABL   RLY TYPE  
  TIME MIN        
  FINAL SP   INPUT 1 IN1 TYPE J TC L
  SP RATE DISABL   XMITTER1  
  EU/HR UP     IN1 HI 770.0
  EU/HR DN     IN1 LO 20.00
        RATIO 1 1.000
        BIAS IN1 0.0
ACCUTUNE FUZZY DISABL   FILTER 1 1
  ACCUTUNE DISABL   BURNOUT1 UP
  AT ERROR     EMMISIV1  
           
      INPUT 2 IN2 TYPE  
        XMITTER2  
        IN2 HI  
        IN2 LO  
        RATIO 2  
        BIAS IN2  
        FILTER 2  
        BURNOUT2  
        EMMISIV2  