Checking transformer in the mod motor

  1. Make sure HEATER CONTROL switch is set to OFF.

  2. Make sure there is 120 Vac on the primary winding of the transformer using an ac voltmeter. Check for 24 Vac on its secondary winding. The transformer is defective if there is no voltage on its secondary winding.

Checking resistor board and motor (Fig. 11)

  1. Make sure HEATER CONTROL switch is set to OFF.

  2. Make sure that the dipswitch settings are correct as indicated in Figure 11. Use a ballpoint pen to make sure that switches are fully depressed. (Partially depressed switches have been a problem in the past.)

  3. Make sure its transformer is not defective. Refer to instructions above.

  4. Disconnect wires from terminals R, W and B of the resistor board.

  5. Temporarily connect a short jumper wire from terminals r to b. The motor of the actuator should go to high-fire, which indicates that the motor is okay and its particular circuit on the resistor board is okay. Otherwise, either the motor or the resistor board is bad.

  6. Temporarily connect a short jumper wire from terminals W to R. The motor of the actuator should go to low-fire (if it is not already there), which indicates that the motor is okay and its particular circuit on the resistor board is okay. Otherwise, either the motor or the resistor board is defective and should be replaced.

  7. Remove the resistor board.

  8. Connect the two wires from the secondary side of the transformer to terminals T1 and T2 of the circuit board where the resistor board was removed.

  9. Using a short jumper wire, temporarily connect from terminal R to B on the circuit board. If the motor works, the resistor board is defective and should be replaced.
Figure 11. Resistor board, Heatec PN 5004718, Honeywell PN 221508A.
DIP SWITCH SETTINGS
1
2
3
4
5
6
7
8
9
10
OPEN
OPEN
OPEN
OPEN
CLOSED
CLOSED
OPEN
CLOSED
OPEN
OPEN

SWITCH IS OPEN WHEN BLUE BAR APPEARS NEXT TO SWITCH NUMBER

← previous page   next page →



Home | Profile | Products - Asphalt | Products - Industrial | Products - Concrete
Literature | Tec-Notes | Parts | Service | Employment | Contacts

Please contact Heatec, Inc. at
Phone (423) 821-5200 | Toll-Free (800) 235-5200 | Fax: (423) 821-7673
5200 Wilson Road | P.O. Box 72760 | Chattanooga, Tennessee 37410

©2007 Astec Industries, Inc. All Rights Reserved.
Legal Notice | Privacy Policy | Webmaster


Hot Oil Heater
Tec-Notes

Model differences of mod motors

Interaction with controls

Common problems and symptoms

Checking & resetting cams

Mod motor wiring diagram

Configuration of cams & switches

Dip switch settings

Replacing mod motor